摘 要:随着国内经济的快速发展,我国机动车保有量增长迅速,加油站与人们的生活联系愈加紧密,由于汽柴油是易燃易爆易挥发的危险品,一旦发生事故后果不堪设想,因此加油站的安全问题越来越引起人们的重视。本文分析总结了加油站的危险性,提出预防措施。
主题词: 加油站;安全;措施
Analysis of Gas Station Security Measures
Zhu Guanghu
(Sinopec Shanxi Xianyang Petroleum Branch Company , ShanxiXianyang, 712035)
Abstract: With the quick development of domestic economy, China's vehicle population growning rapidly. Gas stations and people's lives become more closely linked. Volatile gasoline and diesel is flammable and explosive dangerous goods. The consequences of the accident could be disastrous. The gas station safety has drawn more attention. This paper analyzes and summarizes the risk of gas stations. And propose preventive measures.
Keyword: Gas Station;Security; Measures
1概述
加油站是零售性质的,经营的是易燃易爆的特殊商品,加油站从选址到施工的管理都非常严格。
加油站大致分为两个功能性区域,罐区和加油区。加油区由营业厅、加油岛和车行道组成。罐区是加油站内的危险区域,包括卸油场地和油罐两部分。一般加油站的汽柴油储罐为地下卧式钢罐。汽柴油主要的物化性质[1]有:
(1)易燃性:在有氧气存在,温度达到着火点汽柴油均极易燃烧。
(2)易爆性:汽柴油蒸汽与空气混合,达到爆炸极限后,遇明火或静电等即引起爆炸。
(3)易挥发性:汽油为组分含碳量低,相对密度在0.68-0.75之间,蒸汽比空气重,极易挥发,挥发后沿着地面扩散。
(4)毒性:汽柴油经皮肤或口腔吸收入人体,会对人体伤害,如皮炎中枢神经障碍等。
因此,加油站的安全防护工作[2~4]极为重要,包括防火、防静电、防溢油、可燃气体监测和安全检查等工作。
2 加油站防火要求
2.1储油罐防火要求
储罐是汽柴油储存设施,安全要求高。
(1)加油站的汽柴油储罐应直接埋入地下。汽油储罐严禁设在室内或用盖板掩盖的坑内。储罐容量小于等于15m3,在建筑密度大的地区,宜采用单一品种,只设1油罐,容积不超过10m3,设1台加油泵。特殊情况,如果埋地有困难的,地上或埋设成半地下式也可,但应设防火堤。
(2)油罐的进油管、量油孔、呼吸管等结合管,应设在人孔盖上,量油孔应采用铜尺槽,量油前先防静电,以防止测量过程中静电危害。
(3)呼吸管管径大于等于50mm;呼吸管必须安装阻火器,管口与地面的距离不应小于4m。
(4)地下油管入孔,应设在坚固的操作井内。井盖应用碰撞时不产生火花的材料制成。
(5)地下卧式油罐,要在首尾两端设有两组接地装置,其电阻值不得大于10Ω。罐体与接地极之间的连接导线要做沥青等防腐处理。
2.2加油机安检要求
加油机是汽柴油的出口,安全检查要求严格。
(1)加油机与储油罐之间应用导线连接并接地。严禁带电检修电气设备。
(2)加油机油枪软管,应加强螺旋形金属丝,并用导线与加油机连接。
(3)加油机所采用的电气元件应符合国家标准《爆炸环境用防爆电气设备通用要求》的规定,并有国家指定的检查单位发给的防爆合格证书。各电气元件上必须有明显的防爆标志。
(4)加油机电气设备应选用本质安全型。电源开关应装在站内管理室。
(5)接近加油机的人员应遵循安全指引,不得打电话、吸烟等,检修操作工具应能防静电。检修现场应避免任何火源。